Industrial Metal Fabricators, Inc.
 Engineering Memorandum
     


 

Date: March 12,1996

Subject: SuperVault MH

Multi-Hazard Rated Insulated and Protected Tank Assembly Multi-Hazard testing of the SuperVault MH was conducted by Southwest Research Institute in January 1996. This testing encompassed requirements for both the cylindrical and rectangular styles for all sizes of the SuperVault MH product line. Additionally, the SuperVault MH was tested for Multi-Hazard exposure in accordance with SwRI Test Standard 95-03. Southwest tested the SuperVault MH tanks for resistance to a high intensity liquid pool fire exposure, hose stream resistance, impact (crash) resistance, and puncture (Projectile) resistance in accordance with three industry standards: UFC Standard A-II-F-l (formerly known as UFC Standard 79-7), SwRI Standard 93-01, and UL 2085. Additionally, the tank structure is designed, constructed, and listed for conformance with UL Standard 142.

The fire exposure tests were conducted using the oven method because it requires a much higher heat input than the liquid pool fire method. The higher heat input, uniform exposure to all surfaces of the tank, and the consistent oven environment provide the most conservative design and, as a result, safer fuel storage facilities. The other tests were conducted on the same tank which had undergone the fire testing. Then the tank was subjected to an additional
2000° F, 2 hour fire exposure and easily met all acceptance criteria. This proves that the SuperVault MH possesses and maintains their protection and can be recertified for use after exposure to fire, puncture and impact.

In addition to the tank testing, a Quality Control review was conducted by Southwest Research Institute to establish a product-listing program. As part of the listing program Southwest Research Institute performs surprise quality inspections of our manufacturing plants at least once each quarter. We are authorized to apply labels to the SuperVault tanks indicating that they are listed by Southwest Research Institute.

The SuperVault tanks are the first fully listed Multi-Hazard Rated Insulated and Protected Aboveground Fuel Storage Tanks with a 4 Hour Fire Rating. In addition, the SuperVault MH is the first protected aboveground fuel storage tank to pass not only the minimum UL 2085 testing requirements, but also the very stringent test requirements of SwRI 95-03, SwRI 93-01 and UFC Standard A-II-F-l. The SuperVault MH Cylindrical tanks (250 through 20,000 gallons) and SuperVault MH Rectangular tanks (250 through 2,000 gallons) are fully listed aboveground fuel tanks with the following certifications:

  • Multi-Hazard Rated Aboveground Tank
  • Insulated Aboveground Tank
  • Protected Aboveground Tank
  • Hose Stream Resistance (on fire tested tank)
  • Crash Resistance (on fire tested tank)
  • Projectile Resistance (on fire tested tank)
  • 4 HOUR FIRE RATING
  • All SuperVault MH tank, both
    Cylindrical and Rectangular, are
    Listed to:
             SwRI Standard 95-03
             SwRI Standard 93-01
             UFC Standard A-II-F-l
             UL 2085 Protected
             UL Standard142
Evidence of listing in accordance with all of these standards is attached. To verify our listing contact:

      Gladys Finley, Certification and Product Services
      Southwest Research Institute, Department of Fire Technology
      (210) 522-2424
      gfinley@swri.org

Leslie D. Scott, PE
Chief Engineer